The following is an example of the alarm_def.idt configuration file:
|-* IDT file generated by IDTPOP utility v1.0
* RECORD: ALARM_DEF LIST OF CONFIGURED ALARMS
*
* 0 ALARM_ID Identifies the Alarm
* 1 CLASS_ID Identifies the Class
* 2 alarm_type_id Identifies the Alarm Type
* 3 alarm_msg Raw Alarm Message
* 4 del_opt Delete on A-ACK,R-RESET,AR-ACK AND RESET
* 5 manual_clear_allowed Manual Clear of Alarm flag
* 6 log_opt Log = GARD for Gen, Ack, Reset, Del
* 7 ack_tout Time in minutes before Alarm is ACKed
* 8 clr_tout Time in minutes before Alarm is Cleared
* 9 max_stacked Maximum number of Alarms to Stack
* 10 help_fname Help File Name if available
* 11 log_file Standard or alt log file specification
* 12 description Description of Alarm Definition
* 13 rep_tout Time in minutes before Alarm is Repeated
*
$ALARM_DISABLED|$SYS|$PTM_AM|Alarm Detection disabled for: %s|-
A|N|G|-1|0|0||1||0
$ALARM_ENABLED|$SYS|$PTM_AM|Alarm Detection enabled for: %s|-
A|N|G|-0|0|0||1||0
$ALARM_MODIFIED|$SYS|$PTM_AM|Alarm limits modified for: %s|-
A|N|G|-1|0|0||1||0
$ALARM_RAWLIM|HIGH|$OOR_AL|Point %s has exceeded its Raw Limits|-
AR|N||0|0|0||0||0
$ALARM_RESTORED|$SYS|$PTM_AM|Alarm limits restored for: %s|-
A|N|G|-1|0|0||1||0