Option 3.2.5. Ack and Reset: Alarm Acknowledged and Reset

If manual reset is enabled, a user can simultaneously acknowledge and manually reset an alarm.

The alarm will not be triggered again until the situation returns to the configured acceptable range and then goes back out of the acceptable range.

When Ack and Reset is clicked:

How the Alarm Viewer responds when a user clicks Ack and Reset, depends on what was configured on the Alarm Options tab in the Alarm Definition (or Point Properties) dialog box.

Manual Reset is not Enabled

On Alarm Options

In Alarm Viewer

Alarm ID

Reset is required

Ack and Reset is clicked

Font color changes

Reset is required

Auto acknowledged and reset

Is deleted

Reset is not required

Ack and Reset is clicked or

Auto acknowledged and reset

Is deleted

Manual Reset is Enabled

In Alarm Options

In Alarm Viewer

Alarm ID

Reset is required

Ack and Reset is clicked or

Auto Ack and reset

Is deleted

Reset is not required

Ack and Reset is clicked or

Auto acknowledged and reset

Is deleted

More information

Option 3.2. Ack and/or Reset Buttons: Acknowledge and Reset alarms.