Syntax |
Point.State |
|
Description |
Integer. To return the state of the point's value. |
|
Comments |
Any of the following states may be returned. |
|
|
State |
Description |
|
CP_NORMAL |
Point is in Normal State |
|
CP_ALARM_HIGH |
Point is in Alarm High State. |
|
CP_ALARM_LOW |
Point is in Alarm Low State. |
|
CP_WARNING_HIGH |
Point is in Warning High State. |
|
CP_WARNING_LOW |
Point is in Warning Low State. |
|
CP_ALARM |
Point is in Alarm State. |
|
CP_WARNING |
Point is in Warning State. |
|
CP_AVAILABLE |
Point has gone from Unavailable to Available. |
|
CP_UNAVAILABLE |
Point is Unavailable |
Example |
' Increment the point value by one, if the point is unavailable, ' set it to 0. sub main() Dim MyPoint as new Point MyPoint.Id = "TANK_LEVEL" MyPoint.Get if MyPoint.State = CP_UNAVAILABLE then MyPoint.SetValue = 0 else MyPoint.SetValue = MyPoint.Value + 1 end if end sub |
|
See Also |
Point.Get (method); Point.GetNext (method) |
CIMPLICITY Extensions to Basic |