RCPDownloadEx (function)

Syntax

RCPDownloadEx (filename$[,[recipename$][,[mapname$][, [pointorval$][,ispoint]]]])

Description

Downloads the specified Recipe from the specified Recipe Group using the specified Map.

Comments

The RCPDownloadEx function takes the following parameters:

 

Parameter

Description

 

filename$

Required string containing the name of the Recipe Group file where the Recipe is located. The Recipe Group file must exist

 

recipename$

Optional string containing the name of the Recipe to be Downloaded.

 

mapname$

Optional string containing the name of the Map to be used when Downloading the Recipe.

 

pointorval$

Optional string containing the Batch Point or Batch ID to be used when Downloading the Recipe.

 

ispoint

Optional integer, set to 1 if pointorval$ is a Batch Point.

 

The value returned is one of the following constants.

 

RCP_SUCCESS

Function was successful.

 

RCP_PT_UNAVAIL

Point in recipe was disabled or does not exist.

 

RCP_NO_PERMISSION

Current user has no setpoint permissions for points in recipe.

 

RCP_VAL_OUTSIDE_RANGE

Value to be written to point in recipe is outside setpoint range.

 

RCP_FILER_ERR

Path or file not found

 

RCP_OLE_ERR

OLE error in execution.

 

RCP_UNKNOWN

Error not covered in one of the above.

Example

RCPDownload ("D:\Bread.rgp", "White", "Line1", "Batch of White Bread", 0)

More information

R