On the Device tab in the Point Properties dialog box:
Address |
Point address requirements are device-dependent. For CCM2 communications, the address format is: <memory_type><offset> The memory types you can use are listed in the Supported CCM2 Devices and Memory Types section. |
Update Criteria |
The update criteria determines how the data will be requested. |
|
Select On Change or On Scan for points whose values should be polled by CCM2 communications at regular intervals. |
|
Select On Demand On Scan or On Demand On Change for points whose values should be polled by CCM2 communications at regular intervals when users are viewing them |
When you are configuring Boolean points for memory types that are not bit addressable, you must also enter data in the following field:
Address Offset |
Enter the bit offset that corresponds to the bit position within the word. |
CCM2 point configuration. |