Registers are 16 bit words. You can configure Analog or Boolean point types to read registers.
For Analog point types, enter the
address in the Address
field. For example, R10 specifies Register 10.
For Boolean point types, enter the
register number in the Address field and the bit offset (from
0 to 15) in the Address
Offset field. For example, an address of R25 with an address
offset of 0 specifies the first bit in Register 25, while an
address of R25 and an address offset of 4 specifies the fifth bit
in Register 25.