This example describes the procedure for correctly changing a value to no value in a .csv file when the file is used with the import/export utility.
Enter alarm limit values for a point in the Point Properties dialog box.
Export the file at a command prompt using the import/export utility.
projectname\master>clie export export1.csv
Where
projectname\master> is the path to the project master directory.
clie export is the export command.
export1.csv is the example name of the export file.
Open export1.csv in Notepad or Excel.
The values you entered on the Alarm tab in the Point Properties dialog box display in the export1.csv file.
Change:
100 to 250
50 to " "
Save the file.
Import the file.
projectname\master>clie import export1.csv
Where
projectname\master is the path to the project master directory.
clie import is the import command.
export1.csv is the example name of the .csv file.
Open the Point Properties dialog box.
Result: The values have changed based on your entries (250 and " ").
The changes are also retained in the .csv file when you open it in Notepad or Excel.
Note: If you had not used double-quotes:
100 would change to 250
50 would remain 50.
The value in the .csv file would also revert to 50.