R Data definition. |
|
Digital points to reference individual bits configuration. |
|
Analog points to reference individual bytes, words, or longwords configuration. |
|
Supported addresses. |
R Data definition
R Data |
Is for internal relays. |
R data points |
Are read and write. |
Digital points to reference individual bits
Point Class |
DIGITAL |
Type |
BOOL |
Access |
Read or Read/Write |
Valid Addresses |
Rxxxx, where xxxx is a valid address for your PMC type |
Address Offset |
0-7, for the particular bit you want to reference |
Analog points to reference individual bytes, words, or longwords
Point Class |
ANALOG |
Type |
SINT, INT, or DINT (1, 2, or 4 bytes) |
Access |
Read or Read/Write |
Valid Addresses |
Rxxxx, where xxxx is a valid address for your PMC type |
Address Offset |
none |
Supported addresses
CNC |
PMC Type |
Valid Address Range |
|||
Series 150 |
NA |
R0000-R0999, R2000-R2999 |
|||
|
NB |
R0000-R1499, R9000-R9117 |
|||
|
NB2 |
R0000-R2999, R9000-R9199 |
|||
Series 150i |
NB6 |
R0000-R2999, R9000-R9199 |
|||
Series 160/180-B/C |
SA1 |
R0000-R0999, R9000-R9099 |
|||
|
SB3/SB5/SC3 |
R0000-R1499, R9000-R9117 |
|||
|
SB4/SB6/SC4 |
R0000-R2999, R9000-R9199 |
|||
Series 210-B, 0i-A |
SA1 |
R0000-R0999, R9000-R9099 |
|||
|
SA3 |
R0000-R0999, R9000-R9117 |
|||
Series 160i/180i, 0i-B(SB7) |
SB5 |
R0000-R1499, R9000-R9117 |
|||
SB6 |
R0000-R2999, R9000-R9199 |
||||
|
SB7 |
R0000-R7999, R9000-R9499 |
|||
Series 210i, 0i-B(SA1) |
SA1 |
R0000-R0999, R9000-R9099 |
|||
|
SA5 |
R0000-R0999, R9000-R9117 |
|||
Power Mate |
All |
R0000-R0999, R9000-R9117 |
|||
Power Mate i |
SB5 |
R0000-R1499, R9000-R9117 |
|||
|
SB6 |
R0000-R2999, R9000-R9199 |
|||
CNC |
1st PMC |
*2nd PMC |
*3rd PMC |
||
Series 300i/310i/320i |
|
|
|
||
|
User Range |
R0000-R7999 |
R0000-R1499 |
R0000-R1499 |
|
|
System Range |
R9000-R9499 |
R9000-R9499 |
R9000-R9499 |
* Optional.
PMC BMI Bits |