T Data

T Data definition.

Digital points to reference individual bits configuration.

Analog points to reference individual bytes, words, or longwords configuration.

Supported addresses.

T Data definition

T Data

Is for changeable timers.

T data points

Are read and write.

Digital points to reference individual bits

Point Class

DIGITAL

Type

BOOL

Access

Read or Read/Write

Valid Addresses

Txxxx, where xxxx is a valid address for your PMC type

Address Offset

0-7, for the particular bit you want to reference

Analog points to reference individual bytes, words, or longwords

Point Class

ANALOG

Type

SINT, INT, or DINT (1, 2, or 4 bytes)

Access

Read or Read/Write

Valid Addresses

Txxxx, where xxxx is a valid address for your PMC type

Address Offset

none

Supported addresses

CNC

PMC Type

Valid Address Range

Series 150

NA/NB

T0000-T0079

 

NB2

T0000-T0299

Series 150i

NB6

T0000-T0299

Series 160/180-B/C

SA1/SB3/SB5/SC3

T0000-T0079

 

SB4/SB6/SC4

T0000-T0299

Series 210-B, 0i-A

SA1/SA3

T0000-T0079

Series 160i/180i, 0i-B(SB7)

SB5

T0000-T0079

SB6

T0000-T0299

 

SB7

T0000-T0499,

T9000-T9499

Series 210i, 0i-B(SA1)

SA1/SA5

T0000-T0079

Power Mate

All

T0000-T0079

Power Mate i

SB5

T0000-T0079

 

SB6

T0000-T0299

CNC

1st PMC

*2nd PMC

*3rd PMC

Series 300i/310i/320i

 

 

 

 

Changeable time

T0000-T0499

T0000-T0079

T0000-T0079

 

Variable-timer precision

T9000-T9499

T9000-T9079

T9000-T9079

* Optional

**

 Note: The CRT/MDI panel and the CNC Screens provide the ability to display Timer data as both individual bits, and as word data using the Timer screen. When displayed as word data, the Timer screen manipulates the data and displays the actual data as multiples of 48 or 8. software does not manipulate the data when you configure points as word data.

More information

PMC BMI Bits