Y Data

Y Data definition.

Configure digital points to reference individual bits.

Configure analog points to reference individual bytes, words, or longwords.

Supported addresses.

Y Data definition

Y Data

Is output data:

 

From

PMC

 

To

Machine tool

Y data points

Are read and write.

Digital points to reference individual bits

Point Class

DIGITAL

Type

BOOL

Access

READ or READ/WRITE

Valid Addresses

Yxxxx, where xxxx is a valid address for your PMC type

Address Offset

0-7, for the particular bit you want to reference

Analog points to reference individual bytes, words, or longwords

Point Class

ANALOG

Type

SINT, INT, or DINT (1, 2, or 4 bytes)

Access:

READ or READ/WRITE

Valid Addresses

Yxxxx, where xxxx is a valid address for your PMC type

Address Offset

none

Supported addresses

CNC

PMC Type

Valid Address Range

Series 150

NA/NB/NB2

Y0000-Y0127

Series 150i

NB6

Y0000-Y0127,

Y0200-Y0327

Series 160/180-B/C

SA1/SB3/SB4/SB5/SB6/SC3/SC4

Y0000-Y0127,

Y1000-Y1014,

Y1020-Y1034

Series 210-B, 0i-A

SA1/SA3

Y0000-Y0127,

Y1000-Y1008

Series 160i/180i, 0i-B(SB7)

SB5/SB6/SB7

Y0000-Y0127

 

SB6/SB7

Y0200-Y0327

Series 210i, 0i-B(SA1)

SA1/SA5

Y0000-Y0127

Power Mate

All

Y0000-Y0127,

Y1000-Y1063

Power Mate i

SB5/SB6

Y0000-Y0127,

Y1000-Y1002,

Y1020-Y1051

CNC

1st PMC

*2nd PMC

*3rd PMC

Series 300i/310i/320i

Y0000-Y0127,

Y0200-Y0327,

Y0400-Y0527,

Y0600-Y0727,

Y1000-Y1127**

Y0000-Y0127,

Y0200-Y0327,

Y0400-Y0527,

Y0600-Y0727,

Y1000-Y1127**

Y0000-Y0127,

Y0200-Y0327,

Y0400-Y0527,

Y0600-Y0727,

Y1000-Y1127**

*     Optional

**    Y1000-Y1127 is reserved for PMC management software. No I/O can be allocated in this area. Do not use it in user programs.

More information

PMC BMI Bits