Step 4. View the Report Data for ALARM_LOG or EVENT_LOG

Select the Data worksheet in the CIMPLICITY Alarm Report workbook.

The report contains the following columns:

Column

Definition

timestamp

Local time that the alarm was logged. .

Alarm ID

The alarm identifier of the alarm or event logged. For point alarms, this is the same as the point identifier.

alarm_class

The alarm class of the alarm or event logged. You may filter a report to include only one class of alarm.

resource

The resource of the alarm or event logged.

logged_by

The user or process which caused the alarm or event to be logged. For point alarm generation, this is frequently MASTER_PTM0_RP, the CIMPLICITY Point Manager.

reference

Reference information for the alarm logged.

prev_state

The previous state of the alarm before the event which caused it to be logged. This may be N (normal), G (generated), A (acknowledged), or R (reset).

log_action

The trigger event which caused the alarm to be logged. This may be G (generation), A (acknowledgment), R (reset), or D (manual deletion).

final_state

The final state of the alarm after the trigger event. This may be G (generated), A (acknowledged), R (reset), or D (deleted).

alarm_message

The alarm message for the alarm being logged.

timestamp_utc

UTC time that the alarm was logged.

image\tips.gif Tip: If you save the CIMPLICITY Alarm Report after you generate it, the same data will be display the next time you open the report and select the Data worksheet.

More information

image\Buttongraysm.png

All steps for reporting alarm logged data.