PCIM Special Cautions

You need to know that:

Each time the Genius Communication enabler starts, the data broadcast by the PCIM card is initialized to zero. Previous values are not maintained.

For applications where PCIM cards are broadcasting data and Series 90 processors are present on the bus, you must map the System Configuration Mismatch to a Diagnostic Category rather than the default classification of FATAL on each Series 90 processor.

If you do not modify this classification, the Series 90 will go to a FAULT/STOP category each time the PCIM is initiated.

More information

PCIM port global data broadcast.