For |
Basic Control Engine Project |
|
Purpose |
To specify if the Trace command will output any trace information. The Event Manager Resident Process (EMRP) reads BCE_ENABLE_TRACING when the EMRP is started during project startup. If BCE_ENABLE_TRACING is set to N or n, the Trace command does not output any trace information. It simply returns before checking whether or not TraceEnable has been called. TraceEnable/TraceDisable commands only affect the output of a single running event script thread. However, BCE_ENABLE_TRACING affects all scripts run in the EMRP on a single server. |
|
Value |
Enter one of the following. |
|
|
Y |
Enables the parameter |
|
N |
Disables the parameter |
Default Value |
N |
|
Global parameters. |