For |
Router System Caution: Do not modify this option unless instructed to by GE Fanuc support personnel. |
Purpose |
To specify the maximum number of messages buffered by the Router in its Router to application queue. The first time a queue overflows, it logs the following message to the Status Log: Router to Application queue overflow on port <port_name> Further queue overflows on the same port do not result in any more error messages. When the queue overflows, if the new message is not a response required message, it is dropped. If it is a response-required message, it is not dropped and the queue size can temporarily exceed the specified value. |
Value |
Number (of messages). |
Default Value |
50 |
Global parameters. |