REDUND_PROBE_COUNT

For

Server Redundancy

Project (On both primary and secondary computer)

Purpose

To specify the number of missed probes (within a failover period) before an application is failed over.

Warning: The failover rate should never be modified to less than 3 seconds.

Comments

The failover period is defined as:

REDUND_PROBE_DELAY * (REDUND_PROBE_COUNT + 1)

If more than the REDUND_PROBE_COUNT probes are missed, a failover is started.

Value

Number (of probes)

Default Value

Count

5

 

Failover period

15 seconds

 

More information

Global parameters.