For |
Server Redundancy Project (On both primary and secondary computer) |
|
Purpose |
To specify the number of milliseconds between probes to contact an application. Warning: The fail over rate should never be modified to less than 3 seconds. |
|
Comments |
The fail over period is defined as: REDUND_PROBE_DELAY * (REDUND_PROBE_COUNT + 1) If more than the REDUND_PROBE_COUNT probes are missed, a failover is started. |
|
Value |
Number of milliseconds |
|
Default Value |
Delay |
3000 milliseconds |
|
Failover period |
15 seconds |