On the Device tab in the Point Properties dialog box:
Update Criteria |
The update criteria field determines how the data will be requested. |
|
Select On Change or On Scan for points whose values should be polled by the Honeywell driver at regular intervals. |
Address |
A Honeywell device point address consists of a one or two character alphabetic field followed by an n-digit decimal-numeric field. The numeric field reflects the offset within an addressing domain, of the particular point. The alphabetic fields map to domains according to the following table: |
|
Enter the point address as follows: |
|
Type of Memory |
Address |
Numeric Range |
|
Digital |
Dn |
0 – system-specific (up to 4095) 4096 – system-specific (17 bit models) |
|
Register * |
Rn |
4096 – system-specific |
|
Extended Register * |
ERn |
4096 – system-specific |
|
System Status Register |
Sn |
2048 – 4095 |
Note: Points may be configured to use
any CIMPLICITY point type, however, it is advisable to maintain
consistency between the CIMPLICITY point type and the data
representations supported by the underlying programmable
controller. For example, only 620-12 and 620-16 processors support
floating point numbers. When using other processor types, it is
recommended that you do not configure REAL CIMPLICITY point
type.
Warning: Extreme care should be taken
when referencing Intelligent Module I/O. Honeywell indicates that
references to invalid Intelligent Module I/O may cause
inter-operability issues with programmable control operation.
Honeywell IPC 620 Point Configuration. |