DX9100 I/O Map

The following table shows the valid range of record numbers in each of the DX9100 regions. Depending on the configuration of extension modules installed in the DX9100, not all records may be available in any particular device.

Region

Valid Range

Notes

AI

1–72

Read only

BI

1–72

Read only

AO

1–72

Setpoint sets hold bit.

BO

1–72

Setpoint sets hold bit.

ADF

1–8

 

ADI

1–72

 

BD

1–32

 

LRS

1–64

Read only

PMK

1–240

These values are stored in EEPROM. They are writable but setpoint should be limited in frequency.

PMO

1–96

 

PML

1–96

 

PMA

1–96

 

The following tables show the mapping between the regions and record used in CIMPLICITY point addresses, and the hardware address of points in the DX9100. These mappings are the same as that of the Johnson Controls Metasys Companion product.

More information

Region Analog Input (AI).

Region Binary Input (BI)

Region Analog Output (AO)

Region Binary Output (BO)

Region Internal Floating Point Data (ADF)

Region Internal Integer Data (ADI)

Region Internal Byte Data (BD)

Region Logic Results (LRS)

Region Programmable Module Constants (PMK)

Region Programmable Module Outputs (PMO)

Region Programmable Module Logic (PML)

Region Programmable Module Accumulator (PMA)

About Johnson Controls N2 Bus Communications.