Several APIs exist that give programmed applications some control over the CIMPLICITY login/logout activities. Versions exist in both C callable and basicscript callable forms.
C callable routines
The C callable routines located in corutil.dll are:
COR_I4 GEFCIMPLICITY_setuserpw (TCHAR *proj, TCHAR *CIMPuser, TCHAR *pw)
COR_I4 GEFCIMPLICITY_remuserpw (TCHAR *proj, TCHAR *CIMPuser, TCHAR *pw)
COR_I4 GEFCIMPLICITY_login(TCHAR *proj)
COR_I4 GEFCIMPLICITY_logout(TCHAR *proj)
Notes
These functions are defined in the header
file <inc_path\cor_user_api.h>
To use these API's link with corutil.lib.
The return value can be one of the
following.
COR_SUCCESS
COR_WARNING
COR_FAILURE
Corresponding basic script extensions
CimSetProjectUserPassword(CIMPuser as string, pw as string, proj as string)
CimClearProjectUserPassword(CIMPuser as string, pw as string, proj as string
CimLogin (proj as string)
CimLogout (proj as string)
General Guidelines
The following routines can be called to avoid the CIMPLICITY invoked GUI.
Purpose |
To enable an application to have logins reference the set data |
Routines |
GEFCIMPLICITY_setuserpw() or CimSetProjectUserPassword() |
Description |
Use the routine to set the CIMPLICITY user and corresponding password (if there is one) for the project from which resources are about to be requested, Do this before you request any CIMPLICITY resources.
A logout can happen after all requests for resources have been removed.
|
Purpose |
To enable an application to stop having logins reference the set data |
Routines |
GEFCIMPLICITY_remuserpw() or CimClearProjectUserPassword() |
Description |
The routine:
|
Purpose |
To force a logout of the currently logged in user |
Routine |
|
Description |
After CimLogout is called, either CimLogin must be called or the similar action initiated from the Login Panel, before data can be retrieved again. |
Purpose |
To cause CIMPLICITY to initiate a login sequence |
Routine |
|
Description |
This most likely will be preceded by a call to CimSetProjectUserPassword and CimLogout, to force a change in the currently logged in CIMPLICITY user. |
Simple login/logout example using Basic script. |
|
About the Login/Logout API |