TSERV_<COM> configuration |
|
TSERV_<COM> example |
TSERV_<COM> Configuration
For |
Marquee network Project |
|
Purpose |
To add a Marquee network COM with specifications. |
|
Parameter ID |
TSERV_<COM> Where <COM> is replaced by the COM ID that you specify in the Marquee Ports configuration window in CIMPLICITY.
|
|
Value |
Format |
2 ipa=<ip_address> tp=<ip_port> rd=1 |
|
Where |
|
|
Is replaced by the Port ID that you specify in the Marquee Ports configuration window in CIMPLICITY. |
|
|
<ip_address> |
Is replaced by the IP address of your terminal server. |
|
<ip_port> |
Is replaced by the telnet port number. |
|
rd |
(Reconnect delay) defines the number of seconds to wait before attempting a reconnection on this communication port. A reconnection delay value of 0 will treat a reconnection failure as a fatal error condition, and the Marquee resident process will terminate. Thus, it is recommended that you use an rd of 1 or 2. |
Default |
NA |
TSERV_<COM> Example
Note: This entry indicates that the marquee resident process should communicate with the port on the terminal server:
IP address |
3.26.7.180 |
Telnet port number |
2600 |
Reconnect delay |
1 second |
You would specify COM1 as the Port ID in the Marquee Ports configuration window.
Note: If you open the glb_parms.idt file you will see that the global
parameter is listed in the following format.
TSERV_<COM>|1|2 ipa=<ip_address> tp=<ip_port> rd=1 mt=5
Where
|1| defines the parameter type as a string.
2. Configure a CIMPLICITY Terminal Server port. |