Modicon Controllers

The Modbus RTU Communications option supports reads from the following memory types on Modicon controllers:

Coils

0xxxx or 0xxxxx

Inputs

1xxxx or 1xxxxx

Input Registers

3xxxx or 3xxxxx

Holding Registers

4xxxx or 4xxxxx

General Reference

6yxxxx or 6yxxxxx

Holding Registers as Double Precision

D4xxxx or D4xxxxx

The Modbus RTU Communications option supports writes to the following memory types on Modicon controllers:

Coils

0xxxx or 0xxxxx

Holding Registers

4xxxx or 4xxxxx

General Reference

6yxxxx or 6yxxxxx

Holding Registers as Double Precision

D4xxxx or D4xxxxx

Caution: When writing to Coils (0xxxx or 0xxxxx), memory protect and coil disable are overwritten.

On Modicon controllers, coils that are not programmed in the controller logic program are not automatically cleared on power up. This means that if a coil is set to 1, the output will remain HOT until explicitly set to 0.

Writing to Holding Registers overrides the controller memory protect.

More information

Modbus RTU supported memory types.