The Data Area used to send the sample data with uncompressed timestamping is stored in Holding Registers 40200 through 40213. The sample data being sent is:
|
Register |
Local Example |
Bridge Example |
Network address of sending PLC |
40200 |
0 |
1030(x0406) |
|
40201 |
0 |
0 |
|
40202 |
0 |
0 |
Address of point receiving unsolicited data |
40203 |
30017 |
30017 |
Number of bytes of data. |
40204 |
32770 |
32770 |
First timestamp word |
40205 |
0 |
0 |
Second timestamp word |
40206 |
5 |
5 |
Third timestamp word |
40207 |
14 |
14 |
Fourth timestamp word |
40208 |
1997 |
1997 |
Fifth timestamp word |
40209 |
11 |
11 |
Sixth timestamp word |
40210 |
43 |
43 |
Seventh timestamp word |
40211 |
09 |
09 |
Eighth timestamp word |
40212 |
98 |
98 |
The unsolicited value |
40213 |
21035 |
21035 |
Holding Registers 40203 through 402058 contain a command to the CIMPLICITY Modbus TCP/IP communications enabler to set the value of a point at Input Register 17 to a value of 21035 with a date of May 14, 1997 and time 11:43:09.98.
The network address of the sending programmable controller is the Modbus TCP/IP.
For local data, the path is only 1
address long and the sending controller's IP address is put into
the lower byte of the first holding register. The other two holding
registers are set to zero.
For bridged data, the path may be
5 addresses long. The example above shows the path 6.4.0.0.0.
Sample MSTR Block - Uncompressed Timestamping. |