VersaMax ENIU Memory Map

%I1-%I2048

10001-12048

30001-30128

40001-40128

%AI1-%AI128

 

30129-30256

40129-40256

%Q1-%Q2048

00001-02048

30257-30384

40257-40384

%AQ1-%AQ128

 

30385-30512

40385-40512

FAULT TABLE

 

 

41025-41088

Writeable Memory:

Start Address

End Address

0001

02048

40257

40512

41025

41025

Note:

Array writes for points mapped in the range of 00001-02048 are not supported. 

The same I/O may be addressed via 40257-40384. 

The first coil will correspond to 40257 bit 0.

To clear the fault table, a value of 0 (zero) may be written to 41025. 

Attempts to write any value other than 0 (zero) are not supported.

More information