Adjusting the Communications Time-out Parameter

The communications time-out parameter used by the Mitsubishi A-Series Serial Communications enabler is set to a default value of 7.5 seconds. You can change this parameter in CIMPLICITY software. To do this, add the following record to the Global Parameters file:

COM<port>_TO|1|<value>

Where <port> is the communication port number and <value> is the time out in tenths of seconds. For example,

COM1_TO|1|105

sets the time out for communications on port COM1 to 10.5 seconds.

More information

About Mitsubishi A-Series Serial Communications.