A1SJ71E71-B2 Settings

For the A1SJ71E71-B2 module, the switches of interest are:

Switch

Setting

Description

SW1

OFF

Line is closed when TCP time-out occurs

 

ON

Line is not closed when TCP time-out occurs

SW2

OFF

Use binary communications

 

ON

Use ASCII communications

SW3

OFF

Writes to the programmable controller are disabled when CPU is in RUN state

 

ON

Writes to the programmable controller are enabled when CPU is in RUN state

SW4

OFF

Start initial processing immediately when a message is received (quick start)

 

ON

Start initial processing 20 seconds after delay time when a message is received (normal start)

Note: All switches are set to the OFF position in the factory.

More information

Mitsubishi TCP/IP hardware configuration requirements.