For the A1SJ71E71-B2 module, the switches of interest are:
Switch |
Setting |
Description |
SW1 |
OFF |
Line is closed when TCP time-out occurs |
|
ON |
Line is not closed when TCP time-out occurs |
SW2 |
OFF |
Use binary communications |
|
ON |
Use ASCII communications |
SW3 |
OFF |
Writes to the programmable controller are disabled when CPU is in RUN state |
|
ON |
Writes to the programmable controller are enabled when CPU is in RUN state |
SW4 |
OFF |
Start initial processing immediately when a message is received (quick start) |
|
ON |
Start initial processing 20 seconds after delay time when a message is received (normal start) |
Note: All switches are set to the OFF position in the factory.
Mitsubishi TCP/IP hardware configuration requirements. |