DC_CONNECT_URETRY_CNT

After Mitsubishi TCP/IP communications declares a device "dead", it periodically tries to re-establish communications between poll checks. The default number of tries is 10.

To change the number of retries:

Add the following record to the log_names.cfg file:

DCQ_CONNECT_URETRY_CNT|P|default|10|<retries>

Where

 <retries> is the number of retries to re-establish communications between poll checks.

Important

Larger values will tend to increase the amount of time it takes to recognize that a device has recovered and re-establish the connection.

Smaller values will increase the overhead if there are a number of devices down.

More information

Change timing and performance characteristics.