The following logical names control how addresses are matched with unsolicited messages. By default, Mitsubishi TCP/IP communications matches each register address with either the HEX or DECIMAL addresses or both.
If either <prcnam>_UNSO_HEX or <prcnam>_UNSO_DEC is defined to be TRUE, addresses are matched using only the defined method.
If <prcnam>_UNSO_ALL_TYPES is defined to be true, Mitsubishi TCP/IP communications matches the address with both the HEX and DECIMAL addresses.
If more than one method is defined, the default behavior will take precedence.
The value of <prcnam> is MTCPIP0 in a standard configuration.
The default method is <prcnam>_UNSO_EITHER.
Advanced configuration requirements. |