Please note the following about point addresses for the OMRON device communications enabler:
Letters in address entries can be
upper or lower case
Leading zeros on address numbers
are optional. Example: HR003 is treated the same as HR3.
Address ranges may be limited by
the address space available in the controller device.
The Error Read w/ Clear and Error
Read w/o Clear memory areas are read only - Do not configure points
with these addresses as setpoints. Refer to the C-Series Host Link
Units manual for details on these memory areas.
You can use a Status (ST) point as
a setpoint to set the operating mode of the controller. When
reading Status, the status data from the Status Read response is
returned. This data is different from the data written. Refer to
the C-Series Host Link Units manual for details on Status Read and
Status Write.
Use BOOL Point Types for
Completion flag (TIM and CNT) and Temporary Relay (TR) points.
Status (ST), Error Read w/ Clear
and w/o Clear are not accessible when you communicate with the
programmable controller via a CV bridge.
Point address formats. |