On the Device tab in the Point Properties dialog box:
Address |
For all memory types except %L, enter the memory type and offset in the Address field. The address format is: <memory type><address> For example, to specify Register 1, the address is %R1. All offsets have a minimum value of 1. |
|
The address of %L memory types requires the block name. Block names must be unique over all programs in the programmable controller. Block names cannot begin with a numeric character. The address format is: %L<address><block name> For example, to specify the fifth word in the %L domain in the program block ABC, the address is %L5ABC. |
|
In addition to the standard diagnostic points, you can configure a set of Series 90 TCP/IP Redundancy diagnostic points. The data structure type of all diagnostic points is UINT. |
Update Criteria |
The update criteria determines how the data will be requested. Select On Change or On Scan for points whose values should be polled by Series 90 TCP/IP communications at regular intervals. Select On Demand On Change or On Demand On Scan for points whose values should be polled by Series 90 TCP/IP communications at regular intervals when users are viewing them. |
Point Type |
Select one of the following: For device points, select Normal. For diagnostic points, select Diagnostic. The Series 90 TCP/IP Communications enabler uses standard diagnostic points. |
When you are configuring Boolean points in memory types that are not bit addressable, you must also enter data in the following field:
Address Offset |
Enter the bit offset that corresponds to the bit position within the word. |