The address format for System Data is:
S<LOCATION>
where <LOCATION> is 0 or 1 to select the Poll or Command point.
0 to select the Poll point
1 to select the Command point
Note: Exactly one poll point must be configured for each system device.
Additional Poll Point Configuration
You must also configure the following for a Poll point:
Data Type is INT.
Elements is 1.
Additional Command Point Configuration
You must also configure the following for a Command point:
Data type is STRING.
Elements is 2.
Point address formats. |