Type the following command at the MS-DOS prompt to test the network configuration and the communication between your computer and the PLC:
sharp_diag <Host Name> <Socket Port Number> COM <command> [COM <…> (up to 10 commands)]
If the test succeeds, output with the following format displays:
Host name: <Computer name> PLC name: <PLC name> Port number: <Port number>
<Computer name> is bound to the socket.
<Computer name> is connected to <PLC name>.
Command #1: <…>
Command #1 has been sent to the PLC successfully.
Command #2:…
…
Successfully read data from the PLC. The length of the response message = <…>
…
Response for command #1: <…>
Response for command #2: …
…
Communication between <Computer name> and <PLC name> is disconnected (normal exit).
Example - Communication Verification
For example, if the computer name is ABC123, the configured host name is SHARP and the configured port number is 24576, with two commands:
sharp_diag ABC123 24576 COM a2 com 24 0 0 2 1 0
the output looks like this:
Host name: ABC123 PLC name: SHARP Port number: 24576
ABC123 is bound to the socket.
ABC123 is connected to SHARP.
Command #1: a2
Command #1 has been sent to the PLC successfully.
Command #2: 24 0 0 2 1 0
Command #2 has been sent to the PLC successfully.
Successfully read data from the PLC. The length of the response message = 98
Response for command #1: a2 0 97 3 28 5
Response for command #2: 24 0 0 0 2 1 0 1
Communication between ABC123 and SHARP is disconnected (normal exit).
Sharp TCP/IP Communications test program. |