Original CMM cards did not support the SNP protocol. Other modules in the Series 90 CPU rack may need to be upgraded when upgrading the CPU firmware.
PACSystems Family |
|
Series 90-30 |
|
Series 90-70 family |
|
Series 90 Micro PLCs |
|
VersaMax |
PACSystems Family
It is recommended that the firmware revision for both RX7i and RX3i be at V2.0 or higher.
Proficy Machine Edition v5.0 or higher is required as the programming software.
Series 90-30
It is recommended that the firmware revision for all CPU models be at V6.5 or higher.
The versions for Series 90-30, with CMM communication, use IC693CMM311 with a Series 90-30 Model 331 (CPU IC693CPU331) or higher model number.
Proficy Machine Edition is required as the programming software. Version 3.50 or higher version of Logicmaster 90-30 Software Package Programmer and Configurator. This is optional if a Hand-Held Programmer for Series 90-30 and 90-20 Programmable Controllers is available. The Hand-Held Programmer may be used to configure the CMM. VersaPro 2.02 or higher may also be used.
Series 90-70 family
It is recommended that firmware revision for all CPU models be at V4.12 or higher.
Proficy Machine Edition is required as the programming software. Version 7.0 or higher of the Logicmaster 90-70 Software Package Programmer and Configurator is required to configure a CMM card.
Series 90 Micro PLCs
All CPU models require V2.1 or higher firmware.
The following PLCs have been qualified for use with the SNP Communications option.
CPU |
IC693UDR001HP1 |
|
IC693UDR001GP1 |
All models with a serial interface supporting SNP.
Version 2.02 or higher of VersaPro can be used to configure the serial ports.
About SNP and SNPX Communications. |