You can adjust the timing and performance characteristics of the Toyopuc communications by changing or defining the global parameters listed below.
<PRCNAM>_CONNECTION_TIMEOUT |
|
<PRCNAM>_READ_WRITE_TIMEOUT |
|
<PORT>_BIND_ADDR |
<PRCNAM>_CONNECTION_TIMEOUT
For |
Toyopuc Project |
|
Purpose |
Specify how long the communications enable should wait for a connect operation to complete. |
|
Value |
Number of seconds |
|
Recommended |
5 |
|
Default Value |
10 |
|
<PRCNAM>_READ_WRITE_TIMEOUT
For |
Toyopuc Project |
|
Purpose |
Specify how long the communications enable should wait for a read or write operation to complete |
|
Comment |
|
|
Value |
Number of seconds |
|
Recommended |
3 |
|
Default Value |
10 |
|
<PORT>_BIND_ADDR
For |
Toyopuc Project |
Purpose |
To assign the host name that corresponds to the Ethernet card to be used for Toyopuc communications. |
Comment |
When there are multiple Ethernet cards in the computer and the first connection configured for access by network services is not used, a host name needs to be configured for each card that will by used by a CIMPLICITY Toyopuc port. For each CIMPLICITY Toyopuc port that is using an alternate connection, define a CIMPLICITY project parameter. |
Value |
Host name that corresponds to the Ethernet card to be used for Toyopuc communications. |
Default Value |
First card in the TCP/IP binding order is used. |
About Toyopuc Ethernet Device Communication module. |