(Available with Order Execution Mgt.)
Description
(Range Source) Set Attribute sets the value of a specified attribute on the currently selected item in the Range Source list.
Note: In Range Source, the implicit selection is the first item in the Range Source list.
Parameters
Parameter |
Description |
|
Attribute ID |
(Required) Target attribute ID. Listed attributes are defined in the Attribute Maintenance dialog box. Tip: Click Tools>Attribute Maintenance on the Tracker Configuration window menu bar to open the Attribute Maintenance dialog box. |
|
(Required) Specifies the supplier of the value. Selections are: |
||
|
Selection |
Parameter entry required with selection |
|
Attribute |
|
|
Expression |
|
|
Point |
|
|
Value |
|
Point Name |
(Required if the From parameter is set to Point) Any single point ID. The point's value is assigned to the attribute. |
|
Attribute Value |
(Required if the From parameter is set to Value) Absolute value that will be assigned to the target attribute. The value can contain any character; all values are passed as characters, including number characters. |
|
Project List |
(Optional and used only when the From parameter is set to Attribute) One or more projects separated by commas. Note: If the Project List parameter is used the function block will only look in those projects for the value source. |
|
RegionID |
(Optional and used only when the From parameter is set to Attribute) One or more regions separated by commas. Note: If the RegionID parameter is used, the function block will only look in those regions for the value source. |
|
Region Location |
(Optional and used only when the From parameter is set to Attribute) A region location can be any of the following:
Note: If the Region Location parameter is used, Range Source will only look in the specified location(s) for the value source. The location cannot be a range. |
|
ItemClass |
(Optional and used only when the From parameter is set to Attribute) Class of the items in the source list. |
|
(Required if the From parameter is set to Attribute) ID of the From attribute whose value will be assigned to the target attribute. Listed attributes are defined in the Attribute Maintenance dialog box. Tip: Click Tools>Attribute Maintenance on the Tracker Configuration window menu bar to open the Attribute Maintenance dialog box. |
||
Item Id |
(Optional and used only when the From parameter is set to Attribute) Item from which the attribute value will be copied. |
|
Value Expression |
(Required if the From parameter is set to Expression) Any CIMPLICITY Basic expression will be calculated; the value will be assigned to the target attribute. |
RSA function blocks list. |