Data Source Diagnostic Point

You can create a Data Source point for each logical CIMPLICITY device in a redundant PLC configuration. If configured, the point will be set to one of the following values:

Value

Description

0

No communication on any cable

1

Current data is collected from the Primary PLC over the Primary Cable

2

Current data is collected from the Primary PLC over the Secondary cable.

3

Current data is collected from the Secondary PLC over the Primary Cable.

4

Current data is collected from the Secondary PLC over the Secondary Cable.

5

Current data is collected from the Third PLC over the Primary Cable.

6

Current data is collected from the Third PLC over the Secondary Cable.

The addresses for the Status diagnostic point is:

$DATA_SOURCE

Data Source Point

More information

Series 90 TCP/IP Triplex diagnostic points.