Recommended Configuration for RX7i Devices

  1. Open the Triplex project in Workbench and, from the Tools menu, select Command Prompt.

  2. Type "idtpop device" and press Enter.

  3. Open the device.idt file in a text editor. The device.idt file is located in the project folder (e.g. C:\Program Files\GE Fanuc\Proficy CIMPLICITY\MyTriplexProject).

  4. For the device in question, change the dead_scan_rate from 45 to a smaller number, such as 10, and save the file.

  5. In the Command Prompt window, type "scpop device" and press Enter.

  6. In Workbench, from the Project menu, select Configuration Update. A message appears asking to copy the master configuration data to run-time data.

  7. Click OK.

When you start the project, it should recover 20 to 30 seconds after a failover/recovery.