AlarmEnableRec
Enables alarms by record number on both the Primary and Standby Alarms Servers. This function can be called from Alarm Server or Client and should not be used with a MsgRPC() call to the Alarm Server.
Syntax
AlarmEnableRec(Record [, ClusterName])
Record:
The alarm record number, returned from any of the following alarm functions:
To store this value, use data type Int in Cicode or Long for variable tags (Long needs 4 bytes).
ClusterName:
Specifies the name of the cluster in which the Alarm Server resides. This is optional if you have one cluster or are resolving the alarm server via the current cluster context. The argument is enclosed in quotation marks "".
Return Value
0 (zero) if successful, otherwise an error is returned.
Related Functions
AlarmFirstTagRec, AlarmNextTagRec, AlarmEnable, AlarmDisableRec, MsgRPC
Example
See AlarmDisableRec
See Also