AlarmSumLast
This command is deprecated in this version of CitectSCADA. Use the AlmSummaryLast command instead.
Gets the index of the most recent alarm summary entry. You can use this index in the AlarmSumGet() function to get field data from an alarm record, in the AlarmSumSet() function to change the existing data in that record, or in the AlarmSumDelete() function to delete the record.
To work with a series of alarm summary records, call this function to get the index, and then call AlarmSumPrev() within a loop, to move backwards in the alarm summary.
This function can only be used if the Alarm Server is on the current machine. When the Alarm Server is not in the calling process, this function will become blocking and cannot be called from a foreground task. In this case, the return value will be undefined and a Cicode hardware alarm will be raised.
Syntax
AlarmSumLast( [ClusterName] )
ClusterName:
Specifies the name of the cluster in which the Alarm Server resides. This is optional if you have one cluster or are resolving the alarm server via the current cluster context. The argument is enclosed in quotation marks "".
Return Value
The index of the most recent alarm summary entry, or -1 if no alarm summary entry is found.
Related Functions
AlarmSumGet, AlarmSumSet, AlarmSumDelete, AlarmSumPrev, AlarmSumFirst, AlarmSumNext
Example
/* This function finds all alarm summary entries that match the specified tag and sets the "OffTime" to the time specified. The alarm entry is not acknowledged or set to the off state, the alarm summary "OffTime" field is all that is affected. */
FUNCTION
SumSetTime(STRING sTag, INT Time)
INT Index;
STRING Name;
Index=AlarmSumLast();
WHILE Index<>-1 DO
Name=AlarmSumGet(Index,"Tag");
IF Name=sTag THEN
AlarmSumSet(Index,"OffTime",Time);
END
Index=AlarmSumPrev(Index);
END
END