Using CitectSCADA > Compiling and Running a Project > Running the System > Effects of Server Reload on Servers
Effects of Server Reload on Servers

The following sections detail the effects on the history of reloaded Alarm, Trend and Report records. This is dependent on which fields have changed.

A ‘Yes’ in the New Alarm column indicates changes to that field will make a new alarm and delete the old one and therefore the history is not kept.

A ‘Yes’ in the Invalid History column means changes to that field will make the history of that record invalid.

Alarm Servers

Common Alarm fields

Field Name New Alarm Invalid History
Alarm Tag Yes No
Cluster Name Yes No
Alarm Description No No
Alarm Category No No
Help No No
Delay No No
Comment No No
Privilege No No
Area No No
Custom 1..8 No No
Paging No No
Paging Group No No

Analog and Time Stamped Analog Alarm fields

Field Name NewAlarm Invalid History
Variable Tag No Yes
High High No Yes
High No Yes
Low Low No Yes
Low No Yes
SetPoint No Yes
Deviation No Yes
High High Delay No No
High Delay No No
Low Low Delay No No
Low Delay No No
DEviation Delay No No
Rate No Yes
Deadband No Yes
Format No No

Digital and Time Stamped Digital Alarm fields

Field Name New Alarm Invalid History
Variable Tag A No Yes
Variable Tag B No Yes

Time Stamped Alarm fields

Field Name New Alarm Invalid History
Variable Tag No Yes
Timer No Yes

Advanced Alarm fields

Field Name New Alarm Invalid History
Expression No Yes

Multi-Digital Alarm fields

Field Name New Alarm Invalid History
Variable Tag A No Yes
Variable Tag B No Yes
Variable Tag C No Yes
Realarm No Yes
On Function No No
Off Function No No
State No Yes
State Description No No

Argyle Analog Alarm fields

Field Name New Alarm Invalid History
Variable Tag No Yes
SetPoint No Yes
High High No Yes
High No Yes
Low No Yes
Low Low No Yes
Deviation No Yes
Rate No Yes
Deadband No Yes
Format No No
Trigger No No
Latch No No
Control Timeout No No

Trend Servers

Changes to the following properties of trends make existing trend files invalid and result in the creation of a new trend file (renaming the old one for backup):

Changing the scale of a tag will make the trend history invalid.

Effect of reload on a modified Trend:

Field Name New Trend Invalid History
Trend Tag Name Yes No
Cluster Name Yes No
Expression No Yes
Trigger No Yes
Comment No No
Privilege No No
Area No No
Eng Units No No
Format No No

Report Servers

Effect of reload on a modified Report:

Field Name New Reports Invalid History
Report Name Yes No
Cluster Name Yes No
Time No Yes
Period No Yes
Trigger No No
Report File Format No No
Output Device No No
Privilege No No
Area No No

Effect of reload on a modified Accumulator:

Field Name New Accumulators Invalid History
Name Yes No
Cluster Name Yes No
Trigger No Yes
Run Time No Yes
No. of Starts No No
Totaliser Inc No No
Totaliser No No
Comment No No
Privilege No No
Area No No