GETSYSINFO

Function - Returns system information.

Inputs

INFO : DINT  Identifier of the requested information

Outputs

Q : DINT     Value of the requested information or 0 if error

Remarks

The INFO parameter can be one of the following predefined values:

_SYSINFO_TRIGGER_MICROS programmed cycle time in micro-seconds
_SYSINFO_TRIGGER_MS programmed cycle time in milliseconds
_SYSINFO_CYCLETIME_MICROS duration of the previous cycle in micro-seconds
_SYSINFO_CYCLETIME_MS duration of the previous cycle in milliseconds
_SYSINFO_CYCLEMAX_MICROS maximum detected cycle time in micro-seconds
_SYSINFO_CYCLEMAX_MS maximum detected cycle time in milliseconds
_SYSINFO_CYCLESTAMP_MS time stamp of the current cycle in milliseconds (OEM dependent)
_SYSINFO_CYCLEOVERFLOWS number of detected cycle time overflows
_SYSINFO_CYCLECOUNT counter of cycles
_SYSINFO_APPVERSION version number of the application
_SYSINFO_APPSTAMP compiling date stamp of the application
_SYSINFO_CODECRC CRC of the application code
_SYSINFO_DATACRC CRC of the application symbols

In LD language, the operation is executed only if the input rung (EN) is TRUE. The output rung (ENO) keeps the same value as the input rung. In IL, the input must be loaded in the current result before calling the function.

ST Language

Q := GETSYSINFO (INFO);

FBD Language

LD Language

(* The function is executed only if EN is TRUE *)
(* ENO keeps the same value as EN *)

IL Language:

Op1: LD  INFO
     GETSYSINFO
     ST  Q