Applies To:
  • CitectSCADA 1.11, 2.00

Summary:
The online documentation for the CINET Bridge parameter is incorrect. The documentation shows this parameter under the LLC section. The bridge parameter should be under the LAN section in the CITECT.INI file.

[LAN]
Bridge=1

If your CINET network is not communicating correctly, check that the bridge parameter is set correctly.

Also Example 8 - CINet Single Server is incorrect. NODE1 and NODE 2 are the bridges, and should have the BRIDGE parameter set to 2. The Server in this example is not a bridge, and does not need the bridge option set. 


Solution:
The documentation is corrected in Version 1.20 and 2.01 and later. 

Keywords:
 