Applies To:
  • CitectSCADA 1.00, 1.01, 1.10, 1.11, 1.20, 2.00, 2.01

Question: Is it possible to enable the I/O Server driver debug commands on startup of Citect? 

Yes, you can specify a debug string in the protocol section of the CITECT.INI file for your driver (under the option DebugStr). For example, if your driver is TIWAY then use the following setting:

DebugStr=Port1 ALL

This will enable the debug tracing of all commands on Port1 of the Tiway protocol. These options can only be placed in the CITECT.INI file - they are not supported in the parameters database.