  • CitectSCADA 2.01

In Version 2.01 an enhancement has been implemented that provides an alternative restoration to the background image after a symbol is deleted. The background image is now restored only under the symbol. If the symbol is a 50 pixel circle, any animation in the boundary region - but outside of the circle - is not over written. This operation is slower than restoring the display in the previous version. If it causes problems, you can disable it with the parameter [ANIMATOR] SymbolOverlap=0. This parameter is 0 by default, so symbols would only be slower if it has been enabled. 

See also Q1098