Applies To:
  • CitectSCADA 1.00, 1.01, 1.10, 1.11, 1.20, 2.00, 2.01

Summary:
Question: When I set the INTL sDate option it is ignored and uses the value from the Windows control panel. What is the problem? 

Solution:
The INTL sDate option must be setup in the CITECT.INI file - not the parameters database. All the INTL options must be setup in the CITECT.INI file as Citect needs to use these variables before the parameters database is loaded. The following [INTL] parameters must be setup in the INI file.

[intl]
iDate=
iTime=
sShortDate=
sLongDate=
sTime=
sDate=
 