With the KF Protocol, writing to several
bits at the same time in the same word was not reliable.
The AB DH-485 Command Set for the SLC500 series provides no method of writing to individual bits. To provide this functionality, the KF driver reads a word from the PLC, modifies a single bit as required, and then writes it back. The driver has bug where writing to bits in the same word is not reliable. |
Solution: |
To work around this problem, put the CITECT.INI setting MaxPending=1 under the [KF] section. The problem has been fixed and will be released in the next version after version 1.20 and 2.01. If you require this fix now, contact Citect Support. |