Applies To:
  • CitectSCADA v1.00, v1.01, v1.10, v1.11, v2.00

Summary:
The logout idle and the last cmd time from the UsrInfor function will not take into account commands executed on Forms. If the operator has a form displayed, and is executing commands on that form, the last command time will not be updated. This may cause the logout idle timeout to occur, and log the operator out of Citect.

Solution:
This problem has been fixed with versions 1.20 and 2.01. The UserInfo last command time will now be updated when a command is executed on a form. Commands are when a call back is executed (i.e. when a button is pressed, check box, etc or the form is closed). Entering keyboard data into the form is not checked. 