  • CitectSCADA 1.00 1.01 1.10 1.11 1.20 2.00 2.01

Summary:
When communicating to a SquareD model 50 PLC using the IZUMI protocol, the communication parameters specified in the manual for an IZUMI PLC will cause a bad or garbled response error message.

Solution:
Either of the following combinations in the Ports database will solve this problem:
 
Data Bits 8 8
Parity ODD NONE
Stop Bits 1 2
 