Applies To:
  • CitectSCADA 1.00 1.01 1.10 1.11 1.20 2.00 2.01

Summary:
This article contains the list of protocol specific error messages. These error messages will be shipped with Citect for Windows version 3.0. However they are still useful for earlier versions of Citect for Windows as you can get the driver error code in the Citect kernel and then lookup the associated error message.

Solution:
The file CITECT\BIN\PROTERR.DBF contains all the protocol specific error messages (version 3.0 and greater only).

A blank protocol field means that error applies to any protocol. A number are in hexadecimal. The mask is used in protocols that have multiple classes of errors. Some drivers have the same set of error codes, they are indicated in this document by a leading digit.

  • MODBUS, MBPLUS 1
  • TIWAY, TISERIAL 2
  • KT, KE, ABKE, ABEI 3
  • FUJI, FUJIT 4
  • RELIANCE, RNET 5

 

PROTOCOL MASK ERROR MESSAGE
0 1 Receive character overrun
0 2 Parity error detected on receive
0 3 Break detected on receive line
0 4 Framing error on receive line
0 5 Receive message is too long
0 6 CRC received is incorrect
0 7 Start of text is not present
0 8 End of text is not present
0 9 Driver has not been initialised
0 A Cannot transmit a message
0 B Cannot reset driver
0 C Length of request inconsistent
0 D Receive message is too short
0 F Invalid command
0 10 Out of timer resources
0 11 Too many channels opened
0 12 Bad channel number specified
0 13 Command cannot be cancelled
0 14 Channel is offline
0 15 No response from device
0 16 Bad unit number specified
0 17 Unit is offline
0 18 Raw data type not supported
0 19 Data type not supported
0 1A Too many units
0 1B Too many commands
0 1D Command cancelled
0 1E Address/length is out of range
0 1F Data length is wrong
0 20 Received data is bad
0 21 Device does not exist
0 22 Device don't support interrupt
0 23 Invalid special options
0 24 Cannot perform write
1MODBUS 0 101 Illegal function
1MODBUS 0 102 Variable address is out of range
1MODBUS 0 103 Address/length is out of range
1MODBUS 0 104 Device failure
1MODBUS 0 105 Acknowledge
1MODBUS 0 106 Busy rejected
1MODBUS 0 107 Negative ack
1MODBUS 0 108 Memory parity error
1MODBUS FF 100 *Modbus exception response code
MODBUS 0 28 Bad response from PLC
MBPLUS 0 28 Unsolicited response from PLC
MBPLUS 0 29 Bad response from PLC
MBPLUS 0 203 Invalid Command
MBPLUS 0 204 Cannot open path to PLC
MBPLUS 0 205 Command Timeout
MBPLUS 0 212 Remote PLC not on line
MBPLUS FF 200 *Modbus Plus NetBIOS error code
GENIUS 0 101 Initialization failure
GENIUS 0 102 PCIM failure
GENIUS 0 103 Invalid segment address
GENIUS 0 104 Invalid I/O port address
GENIUS 0 105 Invalid configuration parameter
GENIUS 0 106 No configuration changes found
GENIUS 0 107 PCIM selected is not initialized
GENIUS 0 108 No data found
GENIUS 0 109 Insufficient data length for device
GENIUS 0 10A Exceeds data length of device
GENIUS 0 10B Device is offline
GENIUS 0 10C PCIM busy
GENIUS 0 10D Invalid message parameter
GENIUS 0 10E Transmit message failure
GENIUS 0 10F No messages available
GENIUS 0 110 No PCIM message activity
GENIUS 0 111 Invalid serial bus address
GENIUS 0 112 Invalid PCIM number
GENIUS 0 113 Error in PCIM firmware
GENIUS 0 114 Duplicate segment values given
GENIUS 0 115 Duplicate IO port values given
GENIUS FF 100 *Genius IO error code
TS01 0 28 Out of memory
TS01 0 29 Received unit init from TS01
TS01 0 2A Attempt to write to protected plc
TS01 0 2B Attempt to read from write protected plc
TS01 0 2C Write 0 to pulse write
TS01 0 2D Bad response to init command
TS01 0 2E Bad response to load address list command
TS01 0 2F Cannot open SDF file
TS01 0 30 More than 231 item read
TS01 0 31 SDF File is not sorted
TS01 0 102 Command inexecutable
TS01 0 104 Device timeout
TS01 0 110 Device stopped
TS01 0 120 Device command memory full
TS01 0 130 RAM-pack active
TS01 0 140 Command not accepted
TS01 0 150 Device uncommunicative
TS01 0 160 Difference in compared lists
TS01 0 170 Command not executed
TS01 0 180 RAM-pack not stapled
TS01 0 1A0 List not completely legible
TS01 0 1B0 Erroneous command
TS01 0 181 Unknown command code
TS01 0 182 Unknown task number
TS01 0 184 Transmission error
TS01 0 190 Message buffer overflow
TS01 FF 100 *TS01 error code
OPTOMUX 0 100 Power-up clear expected
OPTOMUX 0 101 Undefined command
OPTOMUX 0 102 Checksum error
OPTOMUX 0 103 Input buffer overrun
OPTOMUX 0 104 Non-printable ASCII character received
OPTOMUX 0 105 Data field error
OPTOMUX 0 106 Communication link watchdog time-out error
OPTOMUX 0 107 Specified limits invalid
OPTOMUX FF 100 *OPTOMUX error code
OMRON 0 28 Bad response from PLC
OMRON 0 29 Bad special options in ports database
OMRON 0 101 Not executable in RUN mode
OMRON 0 102 Not executable in MONITOR mode
OMRON 0 103 Not executable with PROM mounted
OMRON 0 104 Address over (data overflow)
OMRON 0 10B Not executable PROGRAM mode
OMRON 0 10C Not executable DEBUG mode
OMRON 0 10D Not executable LOCAL mode
OMRON 0 110 Parity error
OMRON 0 111 Framing error
OMRON 0 112 Overrun
OMRON 0 113 FCS error
OMRON 0 114 Format error (parameter length error)
OMRON 0 115 Entry number data error
OMRON 0 116 Instruction not found
OMRON 0 118 Frame length error
OMRON 0 119 Not executable
OMRON 0 120 I/O table generation not possible
OMRON 0 1A0 Transmit parity error
OMRON 0 1A1 Transmit framing error
OMRON 0 1A2 Transmit overrun
OMRON 0 1A3 Transmit FCS error
OMRON 0 1A4 Transmit format error
OMRON 0 1A5 Transmit entry number data error
OMRON 0 1A8 Transmit frame length error
OMRON 0 1B0 Unexecutable
OMRON FF 100 *OMRON error code
MELSEC 0 28 Wrong station number in response
MELSEC 0 100 Write disable
MELSEC 0 101 Parity error
MELSEC 0 102 Check sum error
MELSEC 0 103 Protocol error
MELSEC 0 104 Framing error
MELSEC 0 105 Overrun error
MELSEC 0 106 Character area error
MELSEC 0 107 Character error
MELSEC 0 108 Access error
MELSEC 0 110 Number error
MELSEC 0 111 Mode error
MELSEC 0 112 Special function specification error
MELSEC 0 118 Remote error
MELSEC 0 121 Special function unit bus error
MELSEC FF 100 *MELSEC error code
4FUJI 0 112 Memory write error
4FUJI 0 120 Command undefined
4FUJI 0 121 Parameter error
4FUJI 0 122 Interlocked
4FUJI 0 124 Abnormal module number
4FUJI 0 132 Memory size over
4FUJI FF 100 *FUJI error code
BAILEY 0 28 Spec out of range
BAILEY 0 29 Incompatible type
BAILEY 0 2A Spec not tunable
BAILEY 0 2B Bad quality warning
BAILEY 0 101 Waiting for loop
BAILEY 0 102 Improper format
BAILEY 0 103 Illegal command
BAILEY 0 104 Index already established
BAILEY 0 105 Block already established another point
BAILEY 0 106 Command too long
BAILEY 0 107 Bad reply from BTM
BAILEY 0 108 Export used As Import
BAILEY 0 109 Repeat CIU restart command
BAILEY 0 10A Undefined index
BAILEY 0 10B Memory full
BAILEY 0 10C Host communication error
BAILEY 0 10D BTM not responding
BAILEY 0 10E Import used as export
BAILEY 0 10F Time-out of plant loop response
BAILEY 0 110 Number out of range
BAILEY 0 111 Illegal key
BAILEY 0 112 Need a restart command
BAILEY 0 114 Message active on loop
BAILEY 0 116 Exception report specification list
BAILEY 0 118 Reply too large
BAILEY 0 119 Illegal station mode command
BAILEY 0 11A Illegal Module number in command
BAILEY 0 11B Time-out between bytes in command
BAILEY 0 11C Index already established (by another computer)
BAILEY 0 11D Point type incompatible with command
BAILEY 0 11E Watchdog time-out
BAILEY 0 11F Checksum compare error
BAILEY 0 120 Destination node off-line
BAILEY 0 121 Callup command required
BAILEY 0 122 CIU error
BAILEY 0 123 CIU busy
BAILEY 0 124 BTM off-line
BAILEY 0 125 Conflict with monitor mode
BAILEY 0 126 Point type
BAILEY 0 127 Destination ring off-line
BAILEY 0 128 Destination node busy
BAILEY 0 129 Destination ring busy
BAILEY 0 164 Undefined message type for target module
BAILEY 0 165 Busy - cannot respond at this time
BAILEY 0 166 Mode for command incompatible with module mode
BAILEY 0 167 Message data out of legal range
BAILEY 0 168 Invalid block number
BAILEY 0 169 Unconfigured block number
BAILEY 0 16A Unreadable block
BAILEY 0 16B Invalid function code for target module
BAILEY 0 16C Incompatible function code and block number
BAILEY 0 16D Insufficient memory to write block
BAILEY 0 16E Module not responding
BAILEY FF 100 *BAILEY error code
2TIWAY 0 100 Primitive is not implemented
2TIWAY 0 101 Data type not defined In PLC
2TIWAY 0 102 Data location out of range
2TIWAY 0 103 Primitive too many data bytes
2TIWAY 0 104 Primitive too Few data bytes
2TIWAY 0 105 Primitive length check error
2TIWAY 0 106 Wrong mode for primitive
2TIWAY 0 107 Unit has disabled comms
2TIWAY 0 108 Written data type not verified+D268
2TIWAY 0 109 Location is write protected
2TIWAY 0 10A Device fails to respond
2TIWAY 0 10B Aborted due to fatal error
2TIWAY 0 10C Data type now is invalid
2TIWAY 0 10D Error encounted with type
2TIWAY 0 10E Primitive not valid for type
2TIWAY 0 10F Data pattern not found
2TIWAY 0 111 Number of blocks too big
2TIWAY 0 112 Block number not defined
2TIWAY 0 113 Data bytes in block too big
2TIWAY 0 114 Data bytes in report too big
2TIWAY 0 115 Primitive not allowed in mode
2TIWAY 0 116 Data type not in PLC
2TIWAY 0 117 Error in unit communications
2TIWAY 0 118 Data type not in NIM
2TIWAY 0 110 Number of location too big
2TIWAY 0 119 Data location out of range
2TIWAY 0 11A Communications not established
2TIWAY 0 11B Store and forward buff is full
2TIWAY 0 11C Data format error
2TIWAY 0 11D Locations to access is zero
2TIWAY 0 180 Exception is unknown
2TIWAY 0 201 Non fatal error
2TIWAY 0 202 Program mode
2TIWAY 0 203 Program mode
2TIWAY 0 204 Program - non fatal error
2TIWAY 0 205 Program - non fatal error
2TIWAY 0 400 Undefined network problem
2TIWAY 0 401 Secondary timed out
2TIWAY 0 402 Tiway I HDLC error
2TIWAY 0 403 Wrong secondary responded
2TIWAY 0 406 Bad (NULL) address
2TIWAY 0 408 Receive buffer overflow
2TIWAY 0 409 Incorrect HDLC block checksum
2TIWAY 0 40A Secondary timeout in middle of message
2TIWAY 0 40B Secondary timeouts
2TIWAY 0 40E Uneven bytes from secondary
2TIWAY 0 484 Unrecognized command code
2TIWAY 0 485 Invalid field with command
2TIWAY 0 486 Host frame too long
2TIWAY 0 487 Host frame too short
2TIWAY 0 488 Not connected to network
2TIWAY 0 489 Missed start of message
2TIWAY 0 48B Message length count error
2TIWAY 0 48C Message check-SUM bad
2TIWAY 0 48D Invalid hex-ASCII character
2TIWAY 0 140B HIU not init by NM
2TIWAY 0 240A Not enough memory for sec
2TIWAY 0 2412 Source id not allocated
2TIWAY 0 2413 Macro type invalid
2TIWAY 0 2414 Macro define too big
2TIWAY 0 2415 Macro buffer not allocated
2TIWAY 0 2416 Macro already enabled
2TIWAY 0 2417 Macro source id wrong
2TIWAY 0 8400 Macro buffer undefined
2TIWAY 0 8410 Macro disabled PLC offline
2TIWAY 0 8412 Macro disabled as HIU reset
2TIWAY 0 8413 Macro disabled as HIU reset
2TIWAY 0 140C No memory for status
2TIWAY 0 140D No memory for source id
2TIWAY 0 140F No channel B
2TIWAY 0 241A To much macro data
2TIWAY 0 3401 Length error NM to HIU
2TIWAY 0 4401 HIU to NM range error
2TIWAY 0 4402 HIU to NM address error
2TIWAY 0 4403 HIU to NM broadcast error
2TIWAY 0 4404 Sec response HDLC bad
2TIWAY 0 8420 Macro response too large
2TIWAY FF 100 *Primitive exception error code
2TIWAY FF 200 *Warning
2TIWAY FF 400 *Command exception
TIDIRECT 0 28 Bad response from PLC
TIDIRECT 0 502 Address out of range
TIDIRECT 0 503 Request data not found
TIDIRECT 0 50A Illegal request in current operation mode
TIDIRECT 0 512 Invalid operation with local/remote mode
TIDIRECT 0 543 Control block does not exist
TIDIRECT 0 54E Cannot write to read-only variable
TIDIRECT FF 500 *Task code error
TOSHIBA 0 28 Bad response from PLC
TOSHIBA 0 101 Command error
TOSHIBA 0 102 Format error
TOSHIBA 0 103 Checksum error
TOSHIBA 0 104 Ending code error
TOSHIBA 0 105 Excessive text length
TOSHIBA 0 108 Time-out
TOSHIBA 0 201 No END instruction
TOSHIBA 0 202 Illegal pair instruction
TOSHIBA 0 203 Program failure
TOSHIBA 0 204 Memory full
TOSHIBA 0 205 Illegal page/circuit number
TOSHIBA 0 206 Mode mismatch
TOSHIBA 0 207 PROM error
TOSHIBA 0 208 Operand error
TOSHIBA 0 209 Erroneous register number/size
TOSHIBA 0 20A I/O mismatch
TOSHIBA 0 20B I/O no sync
TOSHIBA 0 20C Erroneous transmission
TOSHIBA 0 20D Type mismatch
TOSHIBA 0 20E Page full
TOSHIBA FF 100 *Computer link error code
TOSHIBA FF 200 *EX error
TOSHIBA FF 300 *Warning
CCM 0 28 Received bad response to ENQ
CCM 0 29 Received NAK to header request
CCM 0 2A Received NAK to data message
CCM 0 2B Received bad response to data message
CCM 0 2C Last request was not completed
CCM 0 2E PLC is not in RUN mode
CCM 0 2F Received bad response to header request
ISTRON 0 28 Received NAK
ISTRON 0 2F Bad .cfg file
HWELL FF 100 *Honeywell Error
TAYLOR 0 28 Unsolicited response from instrument
TAYLOR 0 29 Invalid FC in response
TAYLOR 0 110 ICN Timeout - No Response fron Instrument
TAYLOR 0 111 CP/ICN Controller Buffer Fail
TAYLOR 0 160 Not Configuring Source
TAYLOR 0 161 In Service Manual
TAYLOR 0 162 Configuration Incomplete
TAYLOR 0 163 Invalid Block
TAYLOR 0 164 Source not Authorized
TAYLOR 0 165 Configuration Error
TAYLOR 0 166 Configuration Source Not Busy
TAYLOR 0 167 Configuration Complete
TAYLOR 0 168 Invalid Bytes
TAYLOR 0 169 In Locked State
TAYLOR 0 16A Configuration Source busy
TAYLOR 0 16B Incorrect Parameter
TAYLOR 0 16C Unacceptable Operator Write
TAYLOR 0 16D Block Off
TAYLOR 0 16E Block Null
TAYLOR 0 16F Mode Incorrect
TAYLOR 0 170 Operator Terminates Conputer
TAYLOR 0 171 Manual pushbutton
TAYLOR 0 172 Computer Termination Initiate
TAYLOR 0 173 Computer Fail
TAYLOR 0 174 Setpoint State Incorrect
TAYLOR 0 175 Invalid Tuning Message
TAYLOR 0 176 R/L Status Incorrect
TAYLOR 0 177 Invalid Message
TAYLOR 0 178 Temporarily Not Tunable
TAYLOR 0 179 Foreground Block Configuration Error
TAYLOR 0 17A Invalid Foreground Request
TAYLOR 0 17B Background Nak
TAYLOR 0 17C Main Algorithm in Hold State
TAYLOR 0 182 ICN Controller Memory Disabled
TAYLOR 0 183 ICN Controller Not Ready
TAYLOR 0 184 ICN Controller Does Not Exist
TAYLOR 0 18A Configuration Error
TAYLOR 0 18B No Valid Configuration
TAYLOR 0 18C Elemnent Size Definition Error
TAYLOR 0 18D Element Data Type Error
TAYLOR 0 18E Undefined Data
TAYLOR 0 18F Data Not accessible
TAYLOR 0 190 Request Not Submitted
TAYLOR 0 191 Data Missing - Write With Too Little or No Data
TAYLOR 0 192 Trend Sample Overflow - more Than 254 Samples Accumulated
TAYLOR 0 193 Too Many Bytes Requested
TAYLOR 0 194 Trend Sample Underflow - Less Than 3 Samples taken
TAYLOR 0 195 In Configuration Mode
TAYLOR 0 196 Not In Configuration mode
TAYLOR 0 197 Undefined Configuration Type
TAYLOR 0 198 Invalid TCN or Instrument Number
TAYLOR 0 199 No Buffer Available in ICN Controller
TAYLOR 0 19A Bad Buffer message - Checksum Error
TAYLOR 0 19B No Message Response Received From Instrument
TAYLOR 0 19C Invalid Trend Function
TAYLOR 0 19D Request Not Received From ICN Controller
TAYLOR 0 19E Message incomplete
TAYLOR 0 19F Message Error - Checksum Error
TAYLOR 0 1A0 Request Not Generated - Due to no Configuration or no buffer
TAYLOR 0 1A1 Request List Empty
TAYLOR 0 1A2 Configuration Undetermined
TAYLOR 0 1A3 Configuration Space Error
TAYLOR 0 1A4 Configuration Write error
TAYLOR 0 1A5 Old Foreground
TAYLOR 0 1A6 Perform Group Not Defined
TAYLOR FF 100 *TAYLOR Instrument error code
SIEMENS FF 100 *SIEMENS REPTEL error code
IZUMI 0 100 Receive error
IZUMI 0 101 PLC size error
IZUMI 0 102 PLC run error
IZUMI FF 100 *IZUMI error
5RNET 0 28 Bad sequenced response from PLC
5RNET 0 29 Bad response type from PLC
5RNET 0 2A Bad acknowledge from PLC
5RNET 0 101 Check sum error
5RNET 0 102 Buffer full
5RNET 0 103 Illegal format
5RNET 0 201 Invalid command number
5RNET 0 202 Invalid parameters
5RNET 0 203 Address out of range
5RNET 0 204 Count error
5RNET 0 206 P.C. running
5RNET 0 207 EEPROM memory error
5RNET 0 208 Sequence not found
5RNET 0 209 Memory protect violation
5RNET 0 20A No memory available
5RNET FF 100 *NAK error
5RNET FF 200 *RELIANCE error
SQUARED 0 10001 Illegal protocol opcode
SQUARED 0 10002 Illegal intermediate code
SQUARED 0 10003 Illegal address attempted
SQUARED 0 10004 Illegal rack address attempted
SQUARED 0 10005 Instruction not allowed
SQUARED 0 10006 Item cannot be found
SQUARED 0 10007 Protected register
SQUARED 0 10008 Protected memory
SQUARED 0 10009 Read-Only register
SQUARED 0 1000A Exceed memory limitations
SQUARED 0 1000B Communications overflow
SQUARED 0 1000C Illegal CPU rack addressing
SQUARED 0 1000D Communications error
SQUARED 0 1000E Operation not allowed in run
SQUARED 0 1000F Communication overflow
SQUARED 0 10010 Register count too large
SQUARED 0 10011 Remote device inactive
SQUARED 0 10013 Illegal read parameter
SQUARED 0 10015 Trying to change a forced bit
SQUARED 0 10016 Forcing function is inhibited
SQUARED 0 10017 Fenced register
SQUARED 0 10018 Non-Forcible register
SQUARED 0 10019 CPU error Check register 8175
SQUARED 0 1001A Rack Addr/ user memory overlap
SQUARED 0 1001B Memory error - clear all op
SQUARED 0 1001C Illegal baud rate selected
SQUARED 0 1001D Illegal route
SQUARED 0 1001E Protected memory inhibit coil
SQUARED 0 10020 Protected memory
SQUARED 0 10021 Data error
SQUARED 0 10023 Write protected
SQUARED 0 10028 Hardware memory security
SQUARED 0 10029 Illegal register write
SQUARED 0 1002B Illegal operation attempted
SQUARED 0 1002F Keyswitch position
SQUARED 0 10030 Programming MCR in sub area
SQUARED 0 10031 I/O register safeguarded
SQUARED 0 10032 Rack address not alterable
SQUARED 0 10033 Missing module
SQUARED 0 10050 Insufficient data
SQUARED 0 10051 Unrecognized command
SQUARED 0 10052 Illegal parameter
SQUARED 0 10053 Illegal source parameter
SQUARED 0 10054 Illegal destination parameter
SQUARED 0 10056 Invalid input channel
SQUARED 0 10057 Invalid output channel
SQUARED 0 10058 Device not available
SQUARED 0 10059 Serial link not established
SQUARED 0 1005A Hardware read fault
SQUARED 0 1005B Hardware write fault
SQUARED 0 1005C Read error
SQUARED 0 1005D Write error
SQUARED 0 10073 Device timeout
SQUARED 0 10076 Illegal device
SQUARED 0 10078 Device required
SQUARED 0 10079 Channel required
SQUARED 0 1007A Route required
SQUARED 0 1007E Same source/destination
SQUARED 0 10081 Invalid register address
SQUARED 0 10083 Write data error
SQUARED 0 10085 Insufficient data for write
SQUARED 0 10087 Invalid read parameter
SQUARED FF 10000 *SQUARE D error
KT 0 1001B Invalid packet size
KT 0 1001C Host cannot access dual port
KT 0 1001D Reply Timeout, Wrong IRQ or bad PLC
KT 0 1001E Buffer not available
KT 0 1001F DH+ interface not initialised, run STARTKT
KT 0 10021 Solicited buffer not available
KT 0 10023 Bad function parameter
KT 0 10025 Invalid channel
KT 0 10026 KT not initialised, run STARTKT
KT 0 10027 KT TXD dual port timeout, run STARTKT
KT 0 10028 Fatal buffer memory allocation error
KT 0 10029 Fatal timer buffer memory allocation error
KT 0 1002A Fatal timer buffer memory corrupted
KT 0 1002B KT channel already opened
KT 0 1002C KT card already allocated
KT 0 1002D Duplicate node address detected
KT 0 1002E KT not found with specified memory address
KT 0 1002F KT not configured for given IRQ level
KT FF 10000 *User interface error
3KE 0 10100 PLC out of buffers
3KE 0 10200 PLC is not online
3KE 0 10300 Duplicated token holder detected
3KE 0 10400 Local port is disconnected
3KE 0 11000 Illegal command or format
3KE 0 12000 Host will not communicate
3KE 0 13000 PLC host is not online
3KE 0 14000 Host hardware fault
3KE 0 15000 Illegal data table address
3KE 0 16000 PLC is write protected
3KE 0 17000 Processor is in program mode
3KE 0 18000 Compatibility file is missing
3KE 0 19000 PLC cannot buffer command
3KE 0 1B000 PLC problem due to download
3KE 0 1F001 Error converting block address
3KE 0 1F002 Insufficient levels in address
3KE 0 1F003 Too many levels in address
3KE 0 1F004 Symbol not found
3KE 0 1F005 Symbol is of improper format
3KE 0 1F006 Invalid address
3KE 0 1F007 File is of wrong size
3KE 0 1F008 Changed situation since start
3KE 0 1F009 File is too large
3KE 0 1F00A Word and count too large
3KE 0 1F00B Access denied
3KE 0 1F00C Resource unavailable
3KE 0 1F00D File is of wrong size
3KE 0 1F00E Shutdown cannot be executed
3KE 0 1F00F File is too large
3KE 0 1F010 Histogram overflow
3KE 0 1F011 Illegal data type
3KE 0 1F012 Bad parameter
3KE 0 1F013 Data table deleted
3KE FF 1F000 *EXT STS Error code
3KE F00 10000 *Local STS error
3KE F000 10000 *Remote STS error
3AB 0 40001 I/O operation in progress.
3AB 0 40002 Invalid DEFINE string.
3AB 0 40003 Invalid Number of Elements to DEFINE.
3AB 0 40004 Invalid Data type.
3AB 0 40005 Invalid Access Rights.
3AB 0 40006 Invalid Module, Pushwheel, or Channel.
3AB 0 40007 Invalid Remote Station Address.
3AB 0 40008 Invalid PLC Processor type.
3AB 0 40009 Invalid Number of DEFINE Parameters.
3AB 0 4000A DEFINE Parameters Conflict.
3AB 0 4000B DEFINE Table Full. You requested more data itemsthan you allocated in DTL_INIT.
3AB 0 4000C Loading DEFINE Table ID Conflict.
3AB 0 4000D DEFINE Input File Error.
3AB 0 4000F Data Item is Read Only. You used DTL_WRITE or DTL_RMW.
3AB 0 40010 Data is Invalid type for Operation. The two datatypes involved in the R/W operation are incompatible.
3AB 0 40011 Not Enough Memory Available. For DTL_INIT:
3AB 0 40012 I/O operation did not complete in time.
3AB 0 40013 Define Table Not Initialized.
3AB 0 40014 Define ID out of range.
3AB 0 40016 PLC Processor type Not Supported.
3AB 0 40017 NOS Timer Error. The INTERCHANGE software could not start the timer.
3AB 0 40018 I/O completed with errors.
3AB 0 40019 Bad parameter Value.
3AB 0 4001A Expected parameter is missing.
3AB 0 4001B I/O Operation Not Attempted.
3AB 0 4001D NOS Message Packet Error. Invalid reply packet received from the network interface.
3AB 0 4001F Data Item is > Max Allowed.
3AB 0 40020 No Such Data Item Defined.
3AB 0 40021 Wait ID out of range.
3AB 0 40022 Too many pending I/O requests. Maximum is 40.
3AB 0 40023 NOS lnitialization Error.
3AB 0 40025 NOS Initialization Error.
3AB 0 40026 Bad DEFINE Address.
3AB 0 40027 DTL System already initialized.
3AB 0 40028 Input string too long.
3AB 0 40029 Data Conversion Error.
3AB 0 4002A PLC-5/250 time invalid. The INTERCHANGE clock istrying to read the PI clock of the resource manager.
3AB 0 4002B VMS error setting time.
3AB 0 4002C Error getting symbol expansion.
3AB 0 4002D Bad application address.
3AB 0 4002E lnvalid Network Interface identifier.
3AB 0 4002F Network Interface already connected.
3AB 0 40030 Bad IP address.
3AB 0 40031 Symbol expansion invalid.
3AB 0 40032 Invalid use of definition.
3AB 0 40033 Invalid number of elements.
3AB 0 40034 Invalid host data type keyword.
3AB 0 40035 Invalid PLC data type.
3AB 0 40036 Invalid Network Interface identifier.
3AB 0 40038 Invalid Network Interface identifier.
3AB 0 40039 No connection to Network Interface.
3AB 0 4003A Receive operation already pending.
3AB 0 4003B Conversion error for READ data.
3AB 0 4003C Conversion error for WRITE data.
3AB 0 4003D Data comparison failure.
3AB 0 4003F Receive operation was cancelled.
3AB 0 40040 Receive operation is not pending.
3AB 0 40041 Session to Network Interface was lost.
3AB 0 40042 Session to Network Interface is established.
3AB 0 40043 DTL_SET_FDS nfds parameter is too small.
3AB 0 40044 Operation not supported.
3AB 0 40045 Bad DTSA_TYPE Station Address.
3AB 0 40046 Bad DTSA_TYPE Communications Channel.
3AB 0 40047 Bad DTSA_TYPE Module-type.
3AB 0 40049 Cannot specify DTL_REJECT for both handlers.
3AB 0 4004A Address specified is not supported by DTL function.
3AB 0 4004B Bad DTSA_TYPE Pushwheel.
3AB 0 4004C Operation cancelled by DTL_DISCONNECT.
3AB 0 4004D N.I. cannot support more connections.
3AB 0 4004E N.I. software revision incompatible.
3AB 0 4004F Duplicate application address.
3AB 0 40050 Application address in use by another user.
3AB 0 40051 I/O was canceled by DTL_UNDEF.
3AB 0 40052 Access mode reserved for PLC-2s.
3AB 0 40054 Archive file format error.
3AB 0 4005A Error accessing disk.
3AB 0 40060 PLC types do not match.
3AB 0 40065 Compare failed.
3AB 0 40066 PLC station has invalid mode for attempted operation.
3AB 0 40067 PLC is faulted.
3AB 0 40068 Compare Utility compare failed.
3AB 0 40069 Compare Utility compare success.
3AB 0 4006A Get Faults Utility - found faults.
3AB 0 4006B Get Faults Utility - found no faults.
3AB 0 4006C Sense Mode Utility - run mode.
3AB 0 4006D Sense Mode Utility - remote run mode.
3AB 0 4006E Sense Mode Utility - test mode.
3AB 0 4006F Sense Mode Utility - remote test mode.
3AB 0 40070 Sense Mode Utility - program mode.
3AB 0 40071 Sense Mode Utility - remote program mode.
3AB 0 40072 DLL Detected WM_QUIT Message.
3AB 0 40073 Error copying PLC image to PLC station.
3AB 0 40074 Image can be copied to PLC station with warnings.
3AB 0 40075 The mode of the PLC station was not changed.
3AB 0 40076 Invalid DTSA_TYPE Address type.
3AB 0 40077 DTSA_TYPE File Name is NULL or Zero.
3AB 0 40078 DTSA_TYPE File Length is Zero.
3AB 0 40079 Invalid DTSA_TYPE File Type.
3AB 0 4007A Server is not loaded.
3AB 0 4007B Server is not running.
3AB 0 4007C Reply buffer is too small.
3AB 0 4007D Bit mask contains illegal bits.
3AB 0 4007E PCCC packet handler is NULL.
3AB 0 4007F Invalid option parameter.
3AB 0 40080 Invalid backlog value.
3AB 0 40081 Can't find subprogram to execute.
3AB FFFF 50000 *NOS internal error
3AB FFFF 20000 *UNIX error, or error from C run-time library
3AB FFFF 30000 *VMS specific error
 