If you are using the CCM protocol to
communicate to a GE series 6 or GE series 5 PLC and the interface
card is a CCM1 you may get any of the following error messages:
Unit Off-line. cannot talk You may also find that the communications fail after many hours of continuous operation (around 10 hours) and require you to reset the CCM1 card. |
Solution: |
To solve these problems you should upgrade the CCM1 card to a CCM2 card. You may also purchase a daughter board to fix the CCM1 communication failure problem from CSW Control Systems in Perth Western Australia Phone (09) 364 9611 FAX (09) 364 6864, att Tony Watkins. |