Applies To:
  • CitectSCADA 1.00 1.01 1.10 1.11 1.20 2.00 2.01

The documentation on the function ServerInfo() is incorrect. In the cicode manual and help for Citect for Windows versions 1.xx and 2.xx the return value is documented as:

RETURN VALUE: 0(zero) if a primary server, 1 if a secondary server.

This is incorrect, the documentation should read:

RETURN VALUE: 1 if a primary server, 0 if a secondary server.


The documentation in Citect for Windows Version 3.00 and later is correct.